Project Description

SCB13 DRY TYPE TRANSFORMER

Model: SCB13 series
Rated capacity: 630kVA、800kVA、1000kVA、1600kVA、3150kVA
Voltage ratio: 10/0.4kV、35/0.4kV
Connection group: Dyn11/Yyn0
No load loss: 135W~2590W
Load loss: 640W~15400W
Short circuit impedance: 4%~6%
Frequency: 50Hz
Technical standard: GB 20052-2020
Quality standard: ISO 9001:2015; ISO 14001:2015

Send Inquiry

Product description

SCB13 transformer refers to epoxy resin dry-type transformer, S is three-phase, C is epoxy resin cast dry-type transformer, and B is transformer coil wound with copper foil material. 10/0.4 means that the rated high voltage side of the transformer is 10kv and the low voltage side is 0.4kv.

Advantage

– Small size and light weight;

– Air cooling, no need for insulating oil for isolation, reduced pollution, easy maintenance and good safety.

– Can make the secondary side of SCB13 dry-type transformer output constant amplitude voltage.

– Can improve the quality of electric energy, can obtain sinusoidal input current and output voltage and can achieve unity power factor, and the voltage and current on both sides of SCB13 dry-type transformer are controllable, so the power factor can be adjusted arbitrarily.

Three-phase dry-type transformer meets product quality standards

Dongrun Electric’s  three-phase dry-type transformer undergoes strict quality control at every stage from input to output to ensure that it fully meets the strict requirements of domestic and international standards.

1. Quality Management System ISO 9001: 2015

The operation of the entire Dongrun Electric system is strictly controlled and managed. This ensures the quality of the product at all stages, from receiving customer requirements to design, materials, production, installation, testing, packaging, delivery, and after-sales, all of which are operated under a strict and tight process.

2. Environmental Management ISO 14001: 2015

Dongrun Electric took the lead in applying the ISO 14001: 2015 environmental management system. The implementation of this process demonstrates Dongrun’s responsibility to a wide range of customers. Dongrun is committed to providing the most environmentally friendly high-quality technical products.

3. Certification Certificate ISO / IEC 17025: 2017

The ISO / IEC 17025: 2017 certification confirms that Dongrun’s technical quality meets the requirements of all specific international testing and calibration laboratory standards. All Dongrun products are fully tested in qualified laboratories before leaving the factory to ensure stable quality and provide customers with absolute peace of mind.

Technical Parameters

Rated capacity No-load loss Load loss impedance
30kva 135 640 4%
50kva 195 900
80kva 265 1240
100kva 290 1410
125kva 340 1660
160kva 385 1910
200kva 445 2270
250kva 515 2480
315kva 635 3120
400kva 705 3590
500kva 835 4390
630kva 965 5290
630kva 935 5360 6%
800kva 1090 6260
1000kva 1270 7310
1250kva 1500 8720
1600kva 1760 10500
2000kva 2190 13000
2500kva 2590 15400