Project Description
SCB12 DRY TYPE TRANSFORMER
Model: SCB12 series
Rated capacity: 50kVA、80kVA、125kVA、160kVA、200kVA、250kVA、315kVA、400kVA、500kVA、630kVA、800kVA、1000kVA、1250kVA、1600kVA、
Voltage ratio: 10/0.4kV、35/0.4kV
Connection group: Dyn11/Yyn0
No load loss: 150W~2880W
Load loss: 710W~17100W
Short circuit impedance: 4%~6%
Frequency: 50Hz
Technical standard: GB 20052-2020
Quality standard: ISO 9001:2015; ISO 14001:2015
Product description
SCB12 transformer refers to epoxy resin dry-type transformer, S is three-phase, C is epoxy resin cast dry-type transformer, and B is transformer coil wound with copper foil material. 10/0.4 means that the rated high voltage side of the transformer is 10kv and the low voltage side is 0.4kv.
Advantage
– Small size and light weight;
– Air cooling, no need for insulating oil for isolation, reduced pollution, easy maintenance and good safety.
– Can make the secondary side of SCB12 dry-type transformer output constant amplitude voltage.
– Can improve the quality of electric energy, can obtain sinusoidal input current and output voltage and can achieve unity power factor, and the voltage and current on both sides of SCB12 dry-type transformer are controllable, so the power factor can be adjusted arbitrarily.
three-phase dry-type transformer meets product quality standards
Dongrun Electric’s three-phase dry-type transformer undergoes strict quality control at every stage from input to output to ensure that it fully meets the strict requirements of domestic and international standards.
1. Quality Management System ISO 9001: 2015
The operation of the entire Dongrun Electric system is strictly controlled and managed. This ensures the quality of the product at all stages, from receiving customer requirements to design, materials, production, installation, testing, packaging, delivery, and after-sales, all of which are operated under a strict and tight process.
2. Environmental Management ISO 14001: 2015
Dongrun Electric took the lead in applying the ISO 14001: 2015 environmental management system. The implementation of this process demonstrates Dongrun’s responsibility to a wide range of customers. Dongrun is committed to providing the most environmentally friendly high-quality technical products.
3. Certification Certificate ISO / IEC 17025: 2017
The ISO / IEC 17025: 2017 certification confirms that Dongrun’s technical quality meets the requirements of all specific international testing and calibration laboratory standards. All Dongrun products are fully tested in qualified laboratories before leaving the factory to ensure stable quality and provide customers with absolute peace of mind.
Technical Parameters
Rated capacity | No-load loss | Load loss | impedance |
---|---|---|---|
30kva | 150 | 710 | 4% |
50kva | 215 | 1000 | |
80kva | 295 | 1380 | |
100kva | 320 | 1570 | |
125kva | 375 | 1850 | |
160kva | 430 | 2130 | |
200kva | 495 | 2530 | |
250kva | 575 | 2760 | |
315kva | 705 | 3470 | |
400kva | 785 | 3990 | |
500kva | 930 | 4880 | |
630kva | 1070 | 5880 | |
630kva | 1040 | 5960 | 6% |
800kva | 1215 | 6960 | |
1000kva | 1415 | 8130 | |
1250kva | 1670 | 9690 | |
1600kva | 1960 | 11730 | |
2000kva | 2440 | 14450 | |
2500kva | 2880 | 17170 |